TY-C10KRS
working way: Rack Mount HF Online UPS
Product Introduction: DSP Digital Controller Application, Highly Adaptable and Flexible Configuration, Fulfill the high requirements of Server Room and Precision Equipment's from all aspects.
Features:
1, Output Power Factor of 0.8 to fulfill the development of all the Load Devices.
2, Total Machine Efficiency up to 90% which will reduct the Power Wastage
3, Smart Battery Management System to extend the Life-Span of the Batteries
4, Wide Input Voltage Range to suit the Worst Power Grid Environment
5. Able to do the Online Maintenance under the Power Supplying Condition to the Load (Optional)
6. Multiple Choices of Communication & Monitoring Port, to know your UPS Condition Anytime and Anywhere
Technical Specifications:
Model |
C10KRS |
Capacity |
10KVA/8KW |
Nominal Voltage |
220VAC |
AC Input Nominal Frequency |
50Hz |
AC Input Voltage Range |
120~275VAC±5 |
AC Input Frequency Range |
(45~55)±0.5Hz |
AC Input Bypass Voltage |
80VACx(1±5%) ~ 285VACx((1±5%) |
Batteries Output Voltage |
Standard 192VDC (Optional 240V) |
Batteries Capacity x Numbers |
192VDC / 12VDC x 16 (Optional to 20 Blocks) |
Batteries Charging Current |
4A |
AC Output Voltage |
220VAC±3% (Invert Output) |
AC Output Frequency |
46-54Hz (Normal AC Output) 50Hz±1% (Abnormal AC Output) |
AC Output Wave Form |
Pure Sine Wave THD <3% (Linear Load), Pure Sine Wave THD <8% (Non-Linear Load) |
AC Output Power Factor | 0.8 |
Overload | 105-125% Convert to Bypass after 1mins |
AC Output Current Peak Factor | 3:1 |
Communication and Monitoring Functions | RS232 (Can Chang 485), Stem Node, Intelligent Slot (Can extend to SNMP, SMS & Others Monitoring Method) |
Weight (kg) | 22 |
Dimension (W x D x H) | 438 x 172 x 500 |
Installation Method | Rack or Wall Mounting |