3C10KS

TY-3C20KS

Model: TY-3C20KS
working way: 3 Phase In/1 Phase Out HF Online UPS
Product Introduction: Special Design to cater for Server Room and Precision Devices High Reliability by using the DSP Digital Controller
Detailed

 

 

Features

1. Maintenance Bypass Switch to enable Zero on UPS Live Placement

2. Double Conversion UPS with 0.8 Power Factor with Up to 90% Efficiency

3. Multiple Communication Port from RS232 to Smart Slot or SNMP and SMS Monitoritng System 

4. Complete Battery Management automatically adjust the Battery Termination Voltage to extend the battery lifespan

5. Optional Self-Maintenance Module can work while the machine still running

The main technical parameters

Model

3C20KS

Capacity

20KVA/16KW

Nominal Voltage

380VAC

AC Input Nominal Frequence 50Hz

AC Input Voltage Range

205~478VAC

AC Input Frequency Range (45~55)±5Hz

AC Inout Bypass Voltage

190~520VAC

Batteries Input Voltage

192VDC (Optional up to 240V)

Batteries Capacity x Qty

12VDC x 16 (Optional up to 20 sets)

Batteries Charging Current

4A

AC Output Voltage

220VAC±1% (Invert Output)

AC Output Frequency

46~54Hz (Normal AC Input) 50Hz±1% (Abnormal AC Input)

AC Output Wave Form

Sine Wave THD<3% (Linear Load) Sine Wave THD<8% (Non-Linear Load)

AC Output Power Factor

0.8

AC Output Overload Cap.

105~125% Bypass after 1mins

Communication & Monitoring Function RS232, Smart Slot (Expand to SNMP or SMS Monitoring System)
Weight 35
Dimension 248 x 620 x 500